Chapter 4: Configuring the Library
Configuring I/E Station Slots
64 Quantum Scalar i40 and Scalar i80 User’s Guide
You will need to bulk load and unload cartridges, disrupting library
operations (see
Bulk Loading Tape Cartridges on page 121).
Note: Before using the I/E station to load and unload cartridges, you
need to unlock the I/E station, which allows you to slide the
magazine out just far enough to access the I/E station slots (see
Unlocking the I/E Station on page 113).
Operator Panel
1 Select Setup > Dedicated Slots > I/E.
2 Press Modify.
3 Use the Up and Down buttons to select a value.
4 Press Apply.
5 Press Exit.
6 Save the library configuration (see Saving the Library Configuration
on page 101).
Web Client
1 Select Setup > I/E Station Slots.
The I/E Station Configuration screen appears. The Current
Settings column lists the number of I/E station slots that are
currently configured.
2 Under the New Settings column, select the number of I/E station
slots to configure.
3 Click Apply.
4 Save the library configuration (see Saving the Library Configuration
on page 101).