10 Description
Specifications
This section lists the physical, electrical, and operational specifications for the SNC 6101.
External dimensions
6.5 cm high x 30.5 cm deep x 25.4 cm wide
2.56 in. high x 12 in. deep x 10 in. wide
Weight
weight: 1.64 kg (3.62 lbs)
Power Consumption
The SNC 6101 receives all its power from the Scalar 100. Maximum power consumption is 30 watts in
active mode. SCSI channel termination power is drawn from the Scalar 100 drive sleds, not the SNC
6101. Power supply status is monitored and reported to the ADIC Management Console.
RJ-45 1
RJ-45 2
Each RJ-45 port provides two connection status LEDs. The green LED is
ON when the cable is plugged into another active network device. It turns
OFF whenever the Ethernet cable is disconnected or the device at the
opposite end is powered down or disconnected. The yellow LED flashes to
signify port activity. At the time of this printing, Ethernet port #2 was
disabled internally.
PWR The PWR (Power) LED is ON whenever the SNC 6101 has power applied.
It flashes if the on-board power sensors determine that power supply
voltages are out of range.
ERR The ERR (Error) LED indicates a fault condition. This may be an over-
temperature condition, fan stalled or other internally detected error
situation.
RDY The RDY (Ready) LED normally flashes when the SNC 6101 has finished
booting. If the RDY LED remains ON or OFF for more than a few seconds,
it indicates a problem. The RDY LED flashes 4 times per second when the
SNC 6101 is running in diagnostic mode.
CAUTION
To ensure proper initialization of the SNC 6101, allow at least one
minute between a Scalar 100 power-down and subsequent power-up.