Chapter 2 Installing the Library
Selecting an Installation Location
12 Quantum|ATL PowerStor L200 Series Library User’s Guide
Selecting an Installation Location 2
When selecting an installation location for the library, consider:
• Space requirements
• Installation surface strength and inclination
• Power and grounding
• Environmental specifications
Space
Requirements
2
The library requires 6 inches space behind it for cables and
connections. The library also requires 6 inches in front of it for
opening and closing the library door. No extra space is required to
either side of the library. To remove and replace the library
enclosure, you need an overhead clearance slightly greater than
the height of the library (see Physical Specifications
on page 62).
Surface Strength
and Inclination
2
Place the library on a clean, level surface. If the library is placed on
a desk or table, make sure it is sturdy enough to support the
library’s weight, 37 pounds (17 kilograms) (empty).
Power and
Grounding
2
The electrical ratings for the library are 100 to 120/200 to 240 VAC,
50/60 Hertz.
Power Cord 2
A 110/120 VAC power cord is supplied with your library. If your
locale does not use 110/120 VAC, the power cord used with this
equipment must meet this criteria:
• A minimum of 18/3 AWG, 60
°C, Type SJT
• UL and CSA certified cordage rated for use at 250 VAC with a
current rating that is at least 125% of the current rating of the
product (in Europe, the cordage must have the HAR mark)